1、拒動(dòng)、誤動(dòng)故障:
1. Misoperation failure:
這種故障是高低壓成套設(shè)備主要的故障,其原因可分為兩類(lèi)。一類(lèi)是因操動(dòng)機(jī)構(gòu)及傳動(dòng)系統(tǒng)的機(jī)械故障造成,具體表現(xiàn)為機(jī)構(gòu)卡澀,部件變形、位移或損壞,分合閘鐵芯松動(dòng)、卡澀,軸銷(xiāo)松斷,脫扣失靈等。另一類(lèi)是因電氣控制和輔助回路造成,表現(xiàn)為二次接線接觸不良,端子松動(dòng),接線錯(cuò)誤,分合閘線圈因機(jī)構(gòu)卡澀或轉(zhuǎn)換開(kāi)關(guān)不良而燒損,輔助開(kāi)關(guān)切換不靈,高低壓電氣成套設(shè)備以及操作電源、合閘接觸器、微動(dòng)開(kāi)關(guān)等故障。
This fault is the main fault of high and low voltage complete sets of equipment, and its causes can be divided into two categories. One is caused by the mechanical failure of the operating mechanism and transmission system, which is specifically manifested in mechanism jamming, component deformation, displacement or damage, opening and closing iron core looseness and jamming, shaft pin looseness, tripping failure, etc. The other is caused by electrical control and auxiliary circuit, which is manifested in poor secondary wiring contact, loose terminal, wrong wiring, burning of opening and closing coil due to mechanism jamming or poor change-over switch, ineffective switching of auxiliary switch, high and low voltage complete electrical equipment, operating power supply, closing contactor, microswitch and other faults.
2、開(kāi)斷與關(guān)合故障:
2. Breaking and closing fault:
這類(lèi)故障是由斷路器本體造成的,對(duì)少油斷路器而言,主要表現(xiàn)為噴油短路、滅弧室燒損、開(kāi)斷能力不足、關(guān)合時(shí)爆炸等。高低壓電氣成套設(shè)備對(duì)于真空斷路器而言,高低壓電氣成套設(shè)備表現(xiàn)為滅弧室及波紋管漏氣、真空度降低、切電容器組重燃、陶瓷管破裂等。
This kind of fault is caused by the circuit breaker itself. For the low oil circuit breaker, it is mainly manifested in short circuit of oil injection, burning loss of arc extinguishing chamber, insufficient breaking capacity, explosion during closing, etc. High and low voltage electrical complete equipment for vacuum circuit breaker, high and low voltage electrical complete equipment is characterized by air leakage of arc extinguishing chamber and bellows, reduction of vacuum degree, re ignition of cutting capacitor bank, rupture of ceramic tube, etc.
高低壓電氣成套設(shè)備
Complete set of high and low voltage electrical equipment
3、外力及其他故障:
3. External force and other faults:
包括異物撞擊,自然災(zāi)害,小動(dòng)物短路等不可知的其他外力及意外故障的發(fā)生。
Including foreign body impact, natural disasters, small animal short circuit and other unknown external forces and accidental failures.
4、絕緣故障:
4. Insulation failure:
絕緣水平是要正確處理作用在絕緣上的各種電壓(包括運(yùn)行電壓和各種過(guò)電壓)、各種限壓措施、絕緣強(qiáng)度這三者之間的關(guān)系。高低壓電氣成套設(shè)備力求使產(chǎn)品做到既又經(jīng)濟(jì),高低壓電氣成套設(shè)備得到佳的經(jīng)濟(jì)效益。高低壓電氣成套設(shè)備在絕緣方面的故障主要表現(xiàn)為外絕緣對(duì)地閃絡(luò)擊穿,內(nèi)絕緣對(duì)地閃絡(luò)擊穿,相間絕緣閃絡(luò)擊穿,雷電過(guò)電壓閃絡(luò)擊穿,瓷瓶套管、電容套管閃絡(luò)、污閃、擊穿、爆炸,提升桿閃絡(luò),CT閃絡(luò)、擊穿、爆炸,瓷瓶斷裂等。
Insulation level is to correctly deal with the relationship between various voltages (including operating voltage and various overvoltage), various voltage limiting measures and insulation strength. High and low voltage electrical complete sets of equipment strive to make products safe and economical, and high and low voltage electrical complete sets of equipment get good economic benefits. The insulation faults of high and low voltage complete electrical equipment are mainly manifested in external insulation flashover and breakdown to ground, internal insulation flashover and breakdown to ground, interphase insulation flashover and breakdown, lightning overvoltage flashover and breakdown, porcelain insulator bushing, capacitor bushing flashover, pollution flashover, breakdown and explosion, lifting rod flashover, CT flashover, breakdown and explosion, porcelain insulator fracture, etc.
Electrical complete sets focus on providing you with fresh industry information. For more questions and wonderful contents, please pay attention to our website: http://m.ywf-lanzhou.com , we will have more wonderful content for you.